Customer's power factor shall be maintained at 90%. Any power
factor below 90% shall be adjusted to 90% by the Department
as follows:
Billing Demand X 90%
Adjusted Billing Demand = Actual Power Factor (in
percent)
The power factor calculation will be at the time
of maximum demand or based on a monthly average, whichever
is lower.
The Department may also require the customer to install
power factor correction equipment as a condition of service.
TOWN
OF MANSFIELD MUNICIPAL ELECTRIC DEPARTMENT
M.D.P.U. #111
|